Dynamic differential target flowmeter

8靶式流量計(動差).png
  • 8靶式流量計(動差).png
ZW - BSL seriesDynamic differential target flowmeterIn 60 s application in the industrial flow measu…

Description:

Products overview:
ZW - BSL seriesDynamic differential target flowmeterIn 60 s application in the industrial flow measurement, is mainly used to solve the high viscosity, low Reynolds number fluid flow measurement, successively experienced pneumatic tables and electric table two stages of development.ZW - BSL series is in the original strain chip target flowmeter measurement principle on the basis of using the new type of capacitive force sensor as measure and sensitive components, and use of modern digital intelligent processing technology and developed a new type of flow meters.
Second, the structure and working principle: 
1, structure, 
ZW - BSL seriesDynamic differential target flowmeterMainly by the measuring tube (shell), new sensors (including choke element), integrating display and output parts.According to the different medium and condition, must choose appropriate sensors, therefore, provide accurate object and parameter measurement, and manufacturers to choose appropriate sensor is the key of the products can be accurate measurement. 
2, working principle 
When medium in the measurement of pipe flow, because of its kinetic energy and target plate pressure difference, and produce on the target plate force, make the target board of trace amounts of displacement, the force is proportional to the square of the velocity with the media, the size of the target plate force of the target bar transfer, make the sensor elastomer produces trace changes, thereby breaking patches of capacitance bridge balance.Generation and corresponding voltage signal flow force on the target board: by the fluid flow characteristics, the influence of flow rate and is proportional to the square of the voltage produced by the bridge.Its mathematical expression is as follows: 
CdA rho V2 / F = 2 
Type: F choke a force (kg) of 
Drag coefficient Cd object 
A choke pieces on the measuring tube axial projection area (was) 
Rho conditions of medium density (kg/m3) 
V medium in the measuring tube average flow velocity (m/s) 
Choke (target) accept force F, the rigid connection of transfer (rod) to the sensor, the sensor produces voltage signal output: V = KF 
Type: V - sensor output voltage (mV), K - proportionality constant, F - choke piece (target) by force (kg), 
The voltage signal after preamplifier, AD conversion and computer treatment, obtains the corresponding instantaneous flow and cumulative total.

Applications:
ZW - BSL seriesDynamic differential target flowmeterWidely used in semi water gas, coke oven gas, heavy oil, residual oil metering, asphalt, liquid paraffin, toluene, sulfuric acid, natural gas, methane chloride, flue gas, sewage, water, etc, and other special medium measurement, resolves the problem for many years the industry flow metering.

Four, the main features:
1, suitable for all kinds of pipe diameter: 15-2000 - mm to bigger.
2, suitable for high and low temperature medium: - 196 ℃ to + 450 ℃.Can accurately measure all kinds of room temperature, high temperature, low temperature condition of the liquid, gas, steam, viscous medium and all kinds of fluid flow.
3, high sensitivity, can measure small flow rate, it can measure the low velocity of 0.08 m/s.
4, suitable for high pressure conditions: 0-42 mpa.
5, have no moving parts, high accuracy.
6, good repeatability, is 0.1 0.08% commonly, fast measurement.
Total 7, accurate measurement, high accuracy, measurement can reach 0.2%.
8, good vibration resistance to electromagnetic interference, can dry calibration, and farmar hanging weight method.
9, body material: carbon steel, 304316316 L.
10, mode of power supply: 3.6 V lithium batteries;24 VDC power supply;Double power supply: 3.6 V lithium battery + 24 VDC power supply.
Five, the technical parameters:
1, the measured medium: liquid.Gas;steam
2, nominal diameter pipeline: 15 ~ 300 mm clamp mounting type: 15-600 - mm plug-in: 100 ~ 2000 mm
3, nominal pressure: 0.6 ~ 42 mpa
4, medium temperature: - 20 ℃ ~ 70 ℃ (room temperature).- 196 ℃ ~ + 450 ℃ (high and low temperature type)
5, accuracy: + / - 0.2%, plus or minus 0.5%, plus or minus 1.0%, plus or minus 1.5%, plus or minus 2.5%
6, scope: 1:3, 1:5, 1:10, 1:10 (gas), 1:10 (steam)
7, compensation type: temperature compensation;Pressure compensation
8, repeatability: 0.1% ~ 0.08%
9, the power supply: machine with a built-in 3.6 V lithium batteries;The 24 VDC power supply source;220 vac (only for fission digital tube display)
10, output form: the display reading values;4 ~ 20 ma (two wire system);Pulse;0 ~ 10 v.RS232 / RS485 (optional)
11, the measuring tube material: carbon steel;304;316 l;Can also according to user requirements to provide
12, explosion-proof marks: the Ann model (ExiallCT4) flameproof (ExiallBT4)
13, protection grade: IP65;IP67
Note: meter flange specifications implement GB/T9115.1-9115.4-2000 series standards, pipeline according to user needs production DN6, DN8, DN10 small flow meter, etc.
Six, fault handling:
(Flowmeter with breakdown self check program, the user through the display screen can be found in part!)
1, when the pipe velocity is zero, the measured medium flow meter of instantaneous flow rate of values are not zero, the main cause of this phenomenon are as follows:
A, levelness, before and after installation flowmeter and target and target pole caused by tilting and produce axial horizontal component of the instantaneous flow exists;
B, flow meter run for a long time, the sensor inner stress release production micro changes;
C, in the process of installation or operation, serious overload caused by zero drift;
You may refer to the above three ways are about flow meter reset steps and methods of treatment.
D, bad earth flowmeter shell;
Processing method: users to ground.
E, target, target and measurement is sundry stuck between;
Processing method: before and after the valve closed flowmeter, excessive parts with tools to loosen flowmeter and bolt connection of the measuring tube, and gently shaking the transition parts or remove and clean up the clutter can be reset as is after.
2, the working process of the flowmeter in appear abnormal value increases, the main cause of this phenomenon are as follows:
A, target and target stem with filamentous and banded sundry;
Methods: reference to deal with sundry method.
B, under the condition of high knot engine-grease, target and target pole have serious engine-grease, make the stress components on the target plate along the measuring pipe axis projection area increase, namely the target piece between the measuring tube and annular flow area is reduced, and under the same flow rate, the sensor stress increases, zui has led to an increased flow of abnormal value;
Processing method: remove the transition parts, use tool to target and target rod and the measuring tube wall engine-grease things clear.
3, measurement error is large, some of the reasons for this phenomenon, its zui the main reason for the following:
A, when installation relative concentricity appear larger displacement meter and connection pipe, sealing gasket is not concentric, thus forming the throttle resistance, greatly influence the measured medium.
Mass flow;
Methods: adjust the install state.
B, the straight pipe before and after the flowmeter is too short, and directly installed the bend before the flow meter, valve, such as great interference flow components measured medium;
Methods: according to the specifications for installation or real flow field to calibrate the flowmeter.
C, by-pass pipe leakage;
Methods: inspection and replace the by-pass pipe.
D, target sheet wrapped around have banded sundry, increases the target bearing;
Processing method clutter processing method: with reference to the front.
4, flow meter with no signal or no, value for its reason mainly has the following four:
A, power poor contact or fall off;
Methods: for the onboard battery meter, check whether the battery pack, contacts are in good condition, and whether there is a battery.For the power converter,
Check the connection between the connecting wires are in good condition, whether the wire conduction, external power supply source is normal.
B, flow meter circuit damage;
Methods: to return factory repair.
C, screen damage;
Methods: change back to factory.
D, customer reception system failure;
Processing method: check, troubleshooting.
5, flowmeter has zero value, during the operation of the main reasons for this phenomenon are as follows:
A, stress components (target) fall off, lead to weak inductive sensor;
Methods: assembly specifications of the same target.
B, no voltage meter sensor output signal;
Processing method: first of all determine whether the sensor is damaged, the specific method is to see the sensor data have any change.
C, the medium flow rate is too small to be tested, below zui small scale flow meter;
Methods: returned to the factory to replace the mechanical components.

Seven, installation instructions:
1, normal temperature, low temperature, high temperature type flowmeter depending on the different working conditions using horizontal, vertical or inverted type installation (the factory check list shall prevail);
2, medium temperature when + 300 degrees above, the user response to flowmeter shell heat insulation measures are taken to prevent thermal radiation damage to the header (header working temperature for 30 to + 70 degrees c), the same work under medium temperature - 100 degrees, also should adopt anti-freezing measures;
3, to guarantee the accuracy of the flowmeter measurement, requirement set straight pipe before and after;
4, in order to ensure the flowmeter in inspection and replacement does not affect the system work, should try to set the by-pass valve (3) and the cut-off valve (1, 2);
5, due to the need of technology can be used vertical installation, the flow direction of medium under test can be bottom-up, also can from top to bottom, but when ordering should explain to the supplier;
6, flow meter diameter and connected to the pipe diameter size is the same as far as possible, to reduce the flow disturbance, caused by measurement error;
7, flowmeter shell must be reliable grounding, without ground conditions should explain to the manufacturer.
Eight, notable matters of installation:
1, measurement before and after the pipe should be straight pipe, the pipe diameter of straight pipe shall be the flowmeter measurement tube diameter is equal, such as pipe diameter with different pipe diameter same reducer connected to the entrance.Meter length of straight pipe upstream side is generally not less than 6 ~ 20 d, according to different upstream choke typing, downstream straight pipe not less than 3-4 d.Is according to the horizontal position calibration, the flowmeter is generally installed in horizontal pipe is used, when must be installed in vertical pipe, must use weighing method for flow meter vertical install state calibrated, direction of flow shall be from bottom to top.
2, for ease of use and maintenance to prevent flowmeter enabled one-way bearing, downstream of the bypass pipe flow meter installed in parallel the installation of a drain pipe, easy cleaning and scavenging for instrument, for measuring smudgy fluid or easy to solidification and crystallization medium more necessary.Target plate and the measuring tube (table) should coaxial installation, according to a certain diameter of the experiment proved that the target plate and pipe center if deviation from 1 mm up and down, can result in a 1% to 2% of the flow coefficient of deviation, but around 1 mm deviation, the effect is obvious;
3, install, explosion-proof target type flow time, should pay attention to check for explosion-proof marks and explosion-proof certification, explosion-proof equipment are in good condition.
4, for small diameter flowmeter, due to the small diameter flowmeter is relatively heavy, in order to prevent the pipe deformation or vibrate at work, should be on the brace flowmeter.For large diameter flowmeter can not setting up support.

Ten, parameter table:

Measured medium

Liquid.Gas;steam

Nominal diameter

flange 15~520mm

Clip mounted 15~500mm

plug-in 65~3200mm

Nominal pressure

0.5~48MPa

0.6~42MPa

0.6~42MPa

Medium temperature

- 200.℃ ~+ 500℃ or higher temperature

precision

Plus or minus 0.2%

Plus or minus 0.5%

Plus or minus 1.0%

Plus or minus 1.5%

Range of degrees

1:3(liquid)

1:10(steam)

1:5(Liquid, gas,)

1:10(Liquid, gas,)

1:10(steam)

Compensation in the form of

Temperature compensation.Pressure compensation

repetitive

0.05%~0.08%

Power supply

Machines prepare lithium batteries (3.6V);The power source 24VDC

The output form

The scene shows;4~20mA Two wire;pulse 0~5V;RS465/RS132;GPRS The wireless remote

Measuring pipe material

Carbon steel;Stainless steel;Can be negotiated according to the requirements of customers to provide

Explosion-proof grade

The Ann model (ExiaIICT4); Flameproof (ExdIICT4)

Protection grade

IP65;IP67

Flange specifications

Flow meter connecting flange specifications GB/T Series of standards, can also according to user requirements of special processing.

Browse:
Return To The Top

分享到:

欧美久久综合网_国产区一区二区三区_亚洲乱码精品一二三四区日韩在线 _一区二区三区不卡视频在线观看
亚洲欧美中文日韩在线| 最新亚洲激情| 亚洲大胆av| 韩国一区二区三区美女美女秀| 久久久99国产精品免费| 亚洲综合欧美| 亚洲免费中文| 亚洲欧美日韩精品| 亚洲一区综合| 午夜精品久久久久久久99热浪潮| 亚洲午夜高清视频| 中日韩美女免费视频网址在线观看| 99riav久久精品riav| 亚洲美女av网站| 亚洲精品美女在线观看播放| 亚洲精品一区二区在线| 久久人人爽人人| 亚洲无限av看| 亚洲专区在线| 午夜精品一区二区三区在线| 亚洲欧美综合精品久久成人| 亚洲私人黄色宅男| 午夜精品久久久久久99热| 欧美一级欧美一级在线播放| 欧美一区二区三区视频在线观看 | 国产精品人人爽人人做我的可爱 | 亚洲天堂久久| 香蕉久久夜色| 亚洲福利视频一区| 一本色道久久综合亚洲精品小说| 在线亚洲自拍| 欧美亚洲专区| 看片网站欧美日韩| 欧美激情第8页| 国产精品国产三级国产专播品爱网| 国产精品美女在线| 国产香蕉97碰碰久久人人| 激情另类综合| 亚洲理伦在线| 香港久久久电影| 亚洲人成亚洲人成在线观看| 在线一区观看| 久久精品欧美| 欧美精品三级在线观看| 国产精品美女xx| 国内精品视频666| 亚洲欧洲一区二区天堂久久| 亚洲免费在线播放| 亚洲国产日韩欧美在线图片| 亚洲少妇中出一区| 久久久福利视频| 欧美日韩免费在线视频| 国产欧美一区二区精品婷婷| 亚洲国产精品成人综合色在线婷婷| 99亚洲一区二区| 欧美中文字幕不卡| 国产精品99久久久久久白浆小说| 欧美在线视屏| 欧美日在线观看| 国内成人在线| 亚洲天堂av图片| 亚洲日本成人| 久久精品国产999大香线蕉| 欧美高清一区| 国产欧美日韩综合一区在线播放| 亚洲国产成人在线播放| 亚洲性夜色噜噜噜7777| 亚洲精品极品| 欧美制服丝袜第一页| 欧美国产欧美亚洲国产日韩mv天天看完整 | 在线一区欧美| 久久久激情视频| 欧美日韩在线看| 一色屋精品视频免费看| 亚洲图片你懂的| 亚洲国产欧洲综合997久久| 欧美一级欧美一级在线播放| 欧美精品免费视频| 国内精品久久久久久影视8 | 欧美成人午夜激情| 国产婷婷一区二区| 在线视频亚洲一区| 亚洲精选成人| 久久综合五月| 国产欧美精品日韩| 一本色道久久综合亚洲精品高清| 亚洲国产成人av好男人在线观看| 西瓜成人精品人成网站| 欧美日本韩国一区| 在线免费观看日本欧美| 香港久久久电影| 亚洲免费中文字幕| 欧美色大人视频| 亚洲激情小视频| 亚洲国产婷婷香蕉久久久久久| 欧美在线观看视频在线 | 亚洲三级免费电影| 91久久精品一区二区别| 久久爱www.| 国产精品视频大全| 一区二区精品在线| 妖精成人www高清在线观看| 欧美成人69| 激情综合电影网| 久久er99精品| 久久精品国产v日韩v亚洲 | 亚洲美女在线看| 亚洲人成艺术| 欧美成人性生活| 一区二区视频欧美| 欧美中在线观看| 久久久久国产精品人| 国产精品一区二区三区观看| 亚洲婷婷在线| 亚洲欧美一区二区三区极速播放| 欧美色图五月天| 夜夜嗨一区二区| 亚洲永久精品大片| 欧美系列精品| 亚洲亚洲精品在线观看| 午夜激情久久久| 国产日韩精品一区二区浪潮av| 亚洲欧美卡通另类91av| 欧美亚洲一区二区三区| 国产精品看片资源| 亚洲欧美伊人| 久久精品在线免费观看| 国内精品美女av在线播放| 亚洲第一网站免费视频| 免费在线播放第一区高清av| 在线日韩中文| 99精品视频免费观看视频| 欧美日本在线一区| 9l国产精品久久久久麻豆| 亚洲影音先锋| 国产日韩欧美视频在线| 久久www成人_看片免费不卡| 久久综合999| 亚洲欧洲日本在线| 中文有码久久| 国产日韩精品一区二区三区在线| 欧美在线视频一区二区三区| 裸体女人亚洲精品一区| 亚洲高清免费视频| 宅男精品视频| 国产乱码精品| 亚洲国产一二三| 欧美日韩国产免费| 亚洲午夜激情免费视频| 久久精品视频一| 亚洲激情另类| 亚洲综合日韩在线| 国内精品一区二区| 99亚洲视频| 国产女优一区| 亚洲精品一区在线观看| 欧美日韩精品久久| 亚洲欧美日韩人成在线播放| 免费观看久久久4p| 一区二区三区黄色| 久久久综合精品| 亚洲精品欧美极品| 欧美一区二区三区久久精品| 精品动漫av| 亚洲一区二区精品在线| 国产亚洲aⅴaaaaaa毛片| 亚洲精品社区| 国产精品日韩欧美大师| 最近中文字幕mv在线一区二区三区四区 | 久久精品99国产精品日本| 欧美精品激情在线观看| 亚洲伊人观看| 欧美fxxxxxx另类| 亚洲女同在线| 欧美精品在线观看| 香蕉久久夜色精品国产使用方法| 欧美大片专区| 午夜一区不卡| 欧美日韩mv| 欧美一区二区三区在线观看| 欧美人牲a欧美精品| 欧美在线视频播放| 欧美日韩午夜剧场| 亚洲第一在线| 国产精品男人爽免费视频1| 亚洲精品视频免费在线观看| 国产欧美在线| 一区二区三区四区精品| 红桃视频国产精品| 午夜精品久久久| 亚洲经典在线| 久久久久一区二区三区四区| 在线一区二区三区四区| 欧美不卡在线视频| 欧美在线观看日本一区| 欧美系列一区| 9人人澡人人爽人人精品| 国精品一区二区三区| 午夜精品理论片| 99在线观看免费视频精品观看|